HP Modular PDUs have a unique architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Modular PDUs consist of two building blocks - the Control Unit (core) and the Extension Bar(s) (sticks). The Control Unit is 1U/0U, and the Extension Bars mount directly to the frame of the rack in multiple locations. Single phase models are available up to 40 amps and can have up to 28 outlets divided across 4 extension bars. Three phase models are core only units with 6 x C19 outlets that can be connected to optional extension bars or directly to components such as BladeSystems enclosures. |
 |
|
 |
 |
|
 |
 |
 |
Increased amperage on the new 3 phase core only units can power multiple BladeSystems.. The new unit uses a standard 3 phase input plug and has 6 x IEC C19 outlets.
|
 |
|
 |
 |
|
 |
 |
 |
Enterprise customers with a dense data center environment requiring rack mount power distribution, ideally using the HP 10000 Series racks
Problems encountered
- Lack of sufficient outlet receptacles and space in the rack
- Difficult to access the PDU outlets
- Cable management
- Lack of flexible solutions with quick and easy installation/deployment
- High amperage support needed for BladeSystems
Solutions provided
- More outlets, increasing the number of outlets up to 36 per modular PDU
- Simplified cable management
- 1U/0U rack space saving design
- Easy to install - all models include mounting brackets required to mount the mPDUs in the HP 9000 and 10000 Series Racks.
|
 |
|
 |
 |
 |
|
|
|
|
|
|
|
16A - HV (WW) |
n/a |
252663-B24 |
Detachable |
IEC 320-C20 |
(14) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 and (1) 16A, 8.2ft, IEC 320 C19-C20 |
24A - LV (NA/JPN) |
1 |
252663-D71 |
Attached |
NEMA L5-30P |
(28) NEMA 5-15R |
None |
24A - HV (NA/JPN) |
n/a |
252663-D72 |
Attached |
NEMA L6-30P |
(28) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 |
Core only 24A - HV (NA/JPN) |
n/a |
252663-D74 |
Attached |
NEMA L6-30P |
(4) IEC 320 C-19 |
None |
32A - HV (INTL) |
n/a |
252663-B31 |
Attached |
IEC 309-32A |
(28) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 |
Core only 32A - HV (INTL) |
n/a |
252663-B33 |
Attached |
IEC 309-32A |
(4) IEC 320 C-19 |
None |
40A - HV (WW) |
2 |
252663-B21 |
Field wired terminal |
Field wired terminal |
(28) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 |
40A - HV (NA/JPN) |
n/a |
252663-D73 |
Attached |
Non-NEMA Locking CS8265C, 50A |
(28) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 |
Core only 40A - HV (NA/JPN) |
n/a |
252663-D75 |
Attached |
Non-NEMA Locking CS8265C, 50A |
(4) IEC 320 C-19 |
None |
40A - HV (INTL) |
n/a |
252663-B32 |
Attached |
IEC-309, 60A, 3 pin |
(28) IEC 320 C-13 |
(2) 10A, 4.5ft, IEC 320 C13-C14 |
Core only 40A - HV (INTL) |
n/a |
252663-B34 |
Attached |
IEC-309, 60A, 3 pin |
(4) IEC 320 C-19 |
None |
24A 3 Phase Core Only (NA/JPN) |
n/a |
AF512A |
Attached |
NEMA L15-30 (3 phase) |
(6) IES 320 C-19 |
None |
16A 3 Phase Core Only (INTL) |
n/a |
AF513A |
Attached |
IEC 309 4 pole, 5 wire 16A |
(6) IES 320 C-19 |
None |
48A 3 Phase Core Only (NA/JPN) |
n/a |
AF511A |
Attached |
IEC 309 3 pole 4 wire 60A |
(6) IES 320 C-19 |
None |
32A 3 Phase Core Only (INTL) |
n/a |
AF513A |
Attached |
IEC 309 4 pole, 5 wire 32A |
(6) IES 320 C-19 |
None |
*Notes:
1 The low volt Extension Bars w/5-15 outlets should ONLY be used with the low volt 24A Modular PDU unit.
2 Hardwiring should be done by a certified on-site electrician.
|
|